Technical characteristics
| Technical characteristics | Modular design |
|
¹ ï/ï |
Parameter |
Power station model | |||||
|
ÝÄ-1000 |
ÝÃÄ-1000 |
ÝÍ-1000 |
ÝÃÍ-1000 | ||||
|
1 |
Rated electric power, kW |
1000 | |||||
|
2 |
Rated voltage, V |
6300 èëè 10500 | |||||
|
3 |
Frequency, Hz |
50 | |||||
|
4 |
Power factor |
0,8 | |||||
|
5 |
Heat power of the heat recovery system, kW |
1400 | |||||
|
Including recovery of exhaust gas heat, kW |
660 | ||||||
|
6 |
Type of the primary engine |
diesel engine 8×Í26/26 |
gas/diesel engine 8ÃÄ×Í26/26 |
burning rude oil 8×Í26/26 |
burning gas/rude oil 8ÃÄ×Í26/26 | ||
|
7 |
Engine speed, rpm |
1000 | |||||
|
8 |
Specific consumption of: -liquid fuel in diesel mode, g/kW h -liquid fuel in gas/diesel mode, kg/h -gas in gas/diesel mode and gas/rude oil mode, nm3/h |
191 - - |
191 15-30 271 |
191 - - |
191 15-30 271 | ||
|
9 |
Engine start |
Electric starter | |||||
|
10 |
Dimensions: (length x width x height*), mm |
13400 õ 3000 õ 3500 | |||||
|
11 |
Service life, years |
20 | |||||
|
12 |
Top end overhaul interval, h |
20000 |
16000 |
12000 |
16000 | ||
|
13 |
Major overhaul interval, h |
60000 - 100000 | |||||
Notes:
* - height without noise silencer and exhaust heat boiler.
Additional data:
- exhaust gas temperature at rated power at noise silencer outlet:
- without recovery system – 450 oC;
- with the recovery system being used - 130°Ñ;
- distance of 3 m between modules is recommended;
- standard control panel provides distance control of a block comprising 2-4 power stations. If necessary control panel providing control of a block of 2-8 power stations can be installed.
- Fuel tank volume – 2325ë;
- Harmful emissions satisfying requirements of GOST Ð51249, ÑÎ è ÑÍ emissions below standards by 15-20%.
Principal single linear diagram of the power section:
AVR – microprocessor-based voltage controller;
QF – generator breaker;
QS1 – linear disconnector;
QS2 – grounding disconnector;
ÒÀ1, ÒÀ2 – current transformer;
ÒV – voltage transformer;
ÑÓ – control system.